This technical report refers to the electrical protection of all 132kV switchgear. These settings may be reevaluated during the commissioning, according to actual and measured values. Protection selectivity is partly considered in this report and could be also re-evaluated. Names of parameters in this calculation may differ from those in the appropriate device.
Technical Data of the Lines
Main Line
Conductor Type | ACSR Lynx |
Length | 27.8 km |
Type | ZM Type Tower |
Positive sequence impedance | 0.1583 + j0.4004 (0.431 ∠68.4°) Ω/ km |
Zero sequence impedance | 0.3246 + j1.228 (1.27 ∠75.2°) Ω/ km |
Current capacity (A) | 487 |
Next Line
Conductor Type | ACSR Lynx |
Length | 36 km |
Type | ZM Type Tower |
Positive sequence impedance | 0.1583 + j0.4004 (0.431 ∠68.4°) Ω/ km |
Zero sequence impedance | 0.3246 + j1.228 (1.27 ∠75.2°) Ω/ km |
Current capacity (A) | 487 |
Protection Settings Calculations for Lines
SEL-311C Distance Protection Settings
Distance Zone
Non-Homogeneous Correction Angle
Load Impedance and Load Encroachment
Power Swing Detection/ Out of Step Detection
Switch on to Fault (SOTF)
Fuse failure scheme OR Loss of Potential (LOP)
SEL-351A Back-up Over Current Settings
Back up over current settings
Technical Data of the Power Transformers
Transformers-1
Type of cooling | ONAN / ONAF |
Vector Group | Dyn11 |
Rated Voltage HV V | 132000 |
Rated Voltage LV (V) | 11500 |
Full Load current HV ( A) | 87.48 / 113.72 |
Full Load current LV (A) | 1004.12 / 1305.35 |
Rated Power ( MVA) | 20 / 26 |
% impedance at the normal tap (12 no.) | 10.15% / 13.20 % |
Type of tap changer | On load |
the voltage at the maximum tap (V) | 145200 |
The voltage at the minimum tap (V) | 118800 |
Transformers- 2
Type of cooling | ONAN / ONAF |
Vector Group | Dyn11 |
Rated Voltage HV (V) | 132000 |
Rated Voltage LV (V) | 11500 |
Full Load current HV ( A) | 43.7 / 56.9 |
Full Load current LV (A) | 502 / 652.7 |
Rated Power ( MVA) | 10 / 13 |
% impedance at the normal tap (12 no.) | 10.15% / 13.20 % |
Type of tap changer | On load |
The voltage at the maximum tap (V) | 145200 |
The voltage at the minimum tap (V) | 118800 |
Protection Settings Calculations for Power Transformers
SEL-787 Transformer Differential Protection
Differential Pick-up
Slope-1 Setting
Slope-2 Setting
Differential Unrestrained (U87P (Un-restrained Differential Pick-up))
2nd HARMONIC
5th HARMONIC
SEL-351A Transformer HV Over Current
Pick-up Setting
51PP (for phase fault element)
51GP (for earth fault element)
Time Multiplier Setting
11 kV Outgoing Protection Settings
SEL-551C LT Over-Current and Earth Fault
CDG21 LT Neutral Standby AC series Earth Fault
To download, contact us:
WhatsApp: +989129613659 info@elecengg.com / saeed61850@gmail.com
Our available courses:
- IEC 61850 Configurator Training (4 Hrs)
- DIGSI 4 Offline Video Training (3 Hrs)
- DIGSI 5 Offline Video Training (7 Hrs)
- ETAP VIDEO Training (5.5)
- PSCAD Video Training (4 Hrs)
- PCM 600 Video Training (4 Hrs)
- MiCOM Relays Training Package (4 Hrs)
- Testing and Commissioning of Protective Relays